Air-cooled dehumidifiers – Far East version
For use in the Far East Region
The Airblast Air-Cooled Dehumidifiers are used for drying air of up to 100% relative humidity (RH) with temperatures from -30 ºC to +40 ºC.
Request a quote
Contact information
Do you have questions about how we can help your company? Send us an email and we’ll get in touch shortly.
- More than 50 years of experience
- Airblast offices in 12 countries
Product description
The applications are numerous and wide spread. Below are some examples:
- Surface treatment during internal blasting and painting of tanks
- Shipping industry, both for permanent and temporary applications
- Controlling humidity levels in production processes
- Protection of equipment sensitive to corrosion
- Climatic improvements in damp areas
Airblast Dehumidifiers is delivered as a complete unit with fans, filters, rotor and controls. The dehumidifier is ready for site installation and connection to standard-size ducting.
Each dehumidifier will be custom designed according to the local conditions and the needs of the customer.

Air cooled dehumidifiers
| DH6000S | DH9000S | DH12000S | DH18000S | |
| Process airflow (m³/hr) | 6000 | 9000 | 12000 | 18000 |
| Compressor power (HP/kW) | 40/30 | 50/37 | 60/45 | 110/82 |
| Compressor capacity (kW/hr) | 150.5 | 191.4 | 207 | 379.6 |
| Process blower (kW) | 5.5 | 11 | 15 | 30 |
| Reheating capacity (kW) | 27 | 27 | 27 | 54 |
| Condenser fans (kW) | 2*2.2 | 3*2.2 | 3*2.2 | 6*2.2 |
| Static pressure (Pa/H2O) | 2000 | 2500 | 3000 | 4000 |
| Power Consumption (kW) | 66.9 | 81.6 | 93.6 | 179.2 |
| Condenser | Copper tube / Aluminium fins | |||
| Evaporator | Copper tube / Copper fins | |||
| External dimension LxWxH (mm) | 2800x2200x2220 | 3800x2300x2420 | 3800x2300x2520 | 5920x2300x2500 |
| Weight (metric ton) | 2.8 | 3.5 | 4 | 7 |
| Discharge dimension (mm) | 2 – Ø 280 | 3 – Ø 280 | 4 – Ø 280 | 6 – Ø 280 |
Note (All Models):
- Power supply: 3-phase plus earth 415V / 50 Hz
- Refrigerant: R22
- Cooling step control: 25%~50%~75%~100%
- Cooling Media: Air
- Discharge condition: 25 ± 3 °C/RH below 45%
- We have the policy to improve our equipment continuously & shall reserve the rights to change the dimensions and specs without prior notice.
Dimensions
| DH6000S | DH9000S | DH12000S | DH18000S | |
| A (mm) | 2800 | 3800 | 3800 | 5920 |
| B (mm) | 2200 | 2300 | 2300 | 2300 |
| C (mm) | 2220 | 2420 | 2520 | 2500 |
| D (mm) | 1300 | 1300 | 1300 | 1300 |